Project check · Step 3 of 3 · Storage project

How much must your battery earn on the power market?

Turn the question around: instead of guessing revenue, state your target – “investment back in 10 years”. The calculator shows the required gap between purchase and sales price, the highest purchase price and how many cycles you need.

1 · Choose a project size

2 · Project and target

Your target and prices

Average of the hours in which you charge.

Average of the hours in which you sell.

365 = one full charge and discharge per day.

System & investment

Use a real supplier quote.

Running costs

Per MWh sold. In Germany, storage commissioned until 2029 is often exempt from grid fees (§ 118(6) EnWG) – check your case.

0 = simple payback.

3 · What must the battery achieve on the power market?

For the project to pay back within 10 years you need:

Required spread (sell − buy)

231 €/MWh

buying at 60 → sell at ≥ €291/MWh

Maximum purchase price

-73 €/MWh

when selling at €140/MWh · Negative = you would have to be paid to charge.

Cycles needed at your prices

1,132 /yr

= 897 MWh sold per year

Investment
€460,000
Traded per year (year 1)
buy 329 MWh · sell 289 MWh
Result year 1 (after costs)
€7,861
Payback at your prices
not within 40 years

Payback by spread (at your purchase price)

Spread €/MWhPayback
40not within 40 years
60not within 40 years
80not within 40 years
100not within 40 years
130not within 40 years
16019.3 years
20012.6 years

For comparison: according to Fraunhofer ISE the mean daily day-ahead price range (max minus min) in Germany was around €130/MWh in 2025, KfW reports €108/MWh. A battery captures less than this range on average, and the range falls as more storage is built.

  • ⚠ At your prices the battery would need more than two full cycles per day – practically unreachable.

Example assumptions, not market data. The project sizes and prices only illustrate the model. Replace every value with quotes, your grid operator's connection offer and your marketer's terms. Taxes, financing and subsidies are not included. Not investment, tax or legal advice.

The calculation

Annual margin = MWh sold × sales price − MWh bought × purchase price − variable costs. Because of losses you buy more than you sell (bought = sold ÷ efficiency). The required margin covers investment, O&M and fixed costs over your target period, including degradation.

What the number means

The required spread is an average over all cycles of a year. If it is well above what marketers offer in your region, the project does not work at these costs – a lower system price, more cycles or extra revenue (self-consumption, peak shaving, balancing) can help.

What we learn

Size changes the maths: small batteries have high costs per kWh and fixed costs spread over few MWh. For small projects pure trading is rarely enough – the opportunity lies in combining it with your own consumption.

Let's talk about your plans.

Site, storage, data center or new markets for your components – write to us and we will get back to you personally.